Nexans RZ1-K secciones en mm²
Nexans RZ1-K secciones en mm²
Flexible Fire Safety cable for fixed installation in low voltage systems.
XLPE/LFH(Low Fire Hazard). 90°C. 0,6/1kV (1,2 kV max). Chilean certificate as type RZ1-K according to SEC protocol PE N° 2/17. Read more1x1.5mm²
Nexans ref.
- Conductor cross-section: 1.5 mm²
- Permissible current rating buried 20°C: 23 A
- Permissible current rating buried/duct 20°C: 19 A
- Perm current rating in duct 30°C: 18 A
- Perm current rating in air 30°C: - A
1x10mm²
Nexans ref. 10012238
- Conductor cross-section: 10 mm²
- Permissible current rating buried 20°C: 98 A
- Permissible current rating buried/duct 20°C: 68 A
- Perm current rating in duct 30°C: 66 A
- Perm current rating in air 30°C: 77 A
1x120mm²
Nexans ref. 10012247
- Conductor cross-section: 120 mm²
- Permissible current rating buried 20°C: 386 A
- Permissible current rating buried/duct 20°C: 263 A
- Perm current rating in duct 30°C: 312 A
- Perm current rating in air 30°C: 400 A
1x150mm²
Nexans ref. 10012248
- Conductor cross-section: 150 mm²
- Permissible current rating buried 20°C: 431 A
- Permissible current rating buried/duct 20°C: 296 A
- Perm current rating in duct 30°C: 342 A
- Perm current rating in air 30°C: 464 A
1x16mm²
Nexans ref. 10012239
- Conductor cross-section: 16 mm²
- Permissible current rating buried 20°C: 126 A
- Permissible current rating buried/duct 20°C: 89 A
- Perm current rating in duct 30°C: 88 A
- Perm current rating in air 30°C: 105 A
1x185mm²
Nexans ref. 10023292
- Conductor cross-section: 185 mm²
- Permissible current rating buried 20°C: 486 A
- Permissible current rating buried/duct 20°C: 332 A
- Perm current rating in duct 30°C: 384 A
- Perm current rating in air 30°C: 533 A
1x2.5mm²
Nexans ref.
- Conductor cross-section: 2.5 mm²
- Permissible current rating buried 20°C: 38 A
- Permissible current rating buried/duct 20°C: 33 A
- Perm current rating in duct 30°C: 24 A
- Perm current rating in air 30°C: - A
1x240mm²
Nexans ref. 10009598
- Packaging: Cut to length (m)
- Conductor cross-section: 240 mm²
- Permissible current rating buried 20°C: 563 A
- Permissible current rating buried/duct 20°C: 382 A
- Perm current rating in duct 30°C: 450 A
- Perm current rating in air 30°C: 634 A
1x25mm²
Nexans ref. 10012241
- Conductor cross-section: 25 mm²
- Permissible current rating buried 20°C: 161 A
- Permissible current rating buried/duct 20°C: 113 A
- Perm current rating in duct 30°C: 117 A
- Perm current rating in air 30°C: 141 A
1x300mm²
Nexans ref.
- Packaging: Cut to length (m)
- Conductor cross-section: 300 mm²
- Permissible current rating buried 20°C: 629 A
- Permissible current rating buried/duct 20°C: 431 A
- Perm current rating in duct 30°C: 514 A
- Perm current rating in air 30°C: 736 A
1x35mm²
Nexans ref. 10012243
- Conductor cross-section: 35 mm²
- Permissible current rating buried 20°C: 194 A
- Permissible current rating buried/duct 20°C: 136 A
- Perm current rating in duct 30°C: 144 A
- Perm current rating in air 30°C: 176 A
1x4mm²
Nexans ref.
- Conductor cross-section: 4 mm²
- Permissible current rating buried 20°C: 59 A
- Permissible current rating buried/duct 20°C: 42 A
- Perm current rating in duct 30°C: 37 A
- Perm current rating in air 30°C: 42 A
1x50mm²
Nexans ref. 10012244
- Conductor cross-section: 50 mm²
- Permissible current rating buried 20°C: 230 A
- Permissible current rating buried/duct 20°C: 159 A
- Perm current rating in duct 30°C: 175 A
- Perm current rating in air 30°C: 216 A
1x6mm²
Nexans ref.
- Conductor cross-section: 6 mm²
- Permissible current rating buried 20°C: 74 A
- Permissible current rating buried/duct 20°C: 52 A
- Perm current rating in duct 30°C: 48 A
- Perm current rating in air 30°C: 55 A
1x70mm²
Nexans ref. 10012245
- Conductor cross-section: 70 mm²
- Permissible current rating buried 20°C: 282 A
- Permissible current rating buried/duct 20°C: 197 A
- Perm current rating in duct 30°C: 222 A
- Perm current rating in air 30°C: 279 A
1x95mm²
Nexans ref. 10012246
- Conductor cross-section: 95 mm²
- Permissible current rating buried 20°C: 339 A
- Permissible current rating buried/duct 20°C: 232 A
- Perm current rating in duct 30°C: 269 A
- Perm current rating in air 30°C: 342 A
3X1.5mm²
Nexans ref. 10043853
- Packaging: Cut to length (m)
- Conductor cross-section: 1.5 mm²
- Permissible current rating buried 20°C: 23 A
- Permissible current rating buried/duct 20°C: 19 A
- Perm current rating in duct 30°C: 19 A
- Perm current rating in air 30°C: 19 A
3X10mm²
Nexans ref.
- Conductor cross-section: 10 mm²
- Permissible current rating buried 20°C: 98 A
- Permissible current rating buried/duct 20°C: 68 A
- Perm current rating in duct 30°C: 60 A
- Perm current rating in air 30°C: 75 A
3X120mm²
Nexans ref.
- Conductor cross-section: 120 mm²
- Permissible current rating buried 20°C: 386 A
- Permissible current rating buried/duct 20°C: 263 A
- Perm current rating in duct 30°C: 268 A
- Perm current rating in air 30°C: 346 A
3X150mm²
Nexans ref.
- Conductor cross-section: 150 mm²
- Permissible current rating buried 20°C: 431 A
- Permissible current rating buried/duct 20°C: 296 A
- Perm current rating in duct 30°C: 300 A
- Perm current rating in air 30°C: 399 A
3X16mm²
Nexans ref.
- Conductor cross-section: 16 mm²
- Permissible current rating buried 20°C: 126 A
- Permissible current rating buried/duct 20°C: 89 A
- Perm current rating in duct 30°C: 80 A
- Perm current rating in air 30°C: 100 A
3X185mm²
Nexans ref.
- Conductor cross-section: 185 mm²
- Permissible current rating buried 20°C: 486 A
- Permissible current rating buried/duct 20°C: 332 A
- Perm current rating in duct 30°C: 340 A
- Perm current rating in air 30°C: 456 A
3X2.5mm²
Nexans ref. 10048200
- Packaging: Cut to length (m)
- Conductor cross-section: 2.5 mm²
- Permissible current rating buried 20°C: 38 A
- Permissible current rating buried/duct 20°C: 33 A
- Perm current rating in duct 30°C: 24 A
- Perm current rating in air 30°C: 32 A
3X240mm²
Nexans ref.
- Conductor cross-section: 240 mm²
- Permissible current rating buried 20°C: 563 A
- Permissible current rating buried/duct 20°C: 382 A
- Perm current rating in duct 30°C: 398 A
- Perm current rating in air 30°C: 538 A
3X25mm²
Nexans ref.
- Conductor cross-section: 25 mm²
- Permissible current rating buried 20°C: 161 A
- Permissible current rating buried/duct 20°C: 113 A
- Perm current rating in duct 30°C: 105 A
- Perm current rating in air 30°C: 127 A
3X35mm²
Nexans ref.
- Conductor cross-section: 35 mm²
- Permissible current rating buried 20°C: 194 A
- Permissible current rating buried/duct 20°C: 136 A
- Perm current rating in duct 30°C: 128 A
- Perm current rating in air 30°C: 158 A
3X4mm²
Nexans ref.
- Conductor cross-section: 4 mm²
- Permissible current rating buried 20°C: 59 A
- Permissible current rating buried/duct 20°C: 42 A
- Perm current rating in duct 30°C: 35 A
- Perm current rating in air 30°C: 42 A
3X50mm²
Nexans ref.
- Conductor cross-section: 50 mm²
- Permissible current rating buried 20°C: 230 A
- Permissible current rating buried/duct 20°C: 159 A
- Perm current rating in duct 30°C: 154 A
- Perm current rating in air 30°C: 192 A
3X6mm²
Nexans ref.
- Conductor cross-section: 6 mm²
- Permissible current rating buried 20°C: 74 A
- Permissible current rating buried/duct 20°C: 52 A
- Perm current rating in duct 30°C: 44 A
- Perm current rating in air 30°C: 54 A
3X70mm²
Nexans ref.
- Conductor cross-section: 70 mm²
- Permissible current rating buried 20°C: 282 A
- Permissible current rating buried/duct 20°C: 197 A
- Perm current rating in duct 30°C: 194 A
- Perm current rating in air 30°C: 246 A
3X95mm²
Nexans ref.
- Conductor cross-section: 95 mm²
- Permissible current rating buried 20°C: 339 A
- Permissible current rating buried/duct 20°C: 232 A
- Perm current rating in duct 30°C: 233 A
- Perm current rating in air 30°C: 298 A
4X1.5mm²
Nexans ref. 10040549
- Packaging: Cut to length (m)
- Conductor cross-section: 1.5 mm²
- Permissible current rating buried 20°C: 23 A
- Permissible current rating buried/duct 20°C: 19 A
- Perm current rating in duct 30°C: 19 A
- Perm current rating in air 30°C: 19 A
4X10mm²
Nexans ref.
- Conductor cross-section: 10 mm²
- Permissible current rating buried 20°C: 98 A
- Permissible current rating buried/duct 20°C: 68 A
- Perm current rating in duct 30°C: 60 A
- Perm current rating in air 30°C: 75 A
4X120mm²
Nexans ref.
- Conductor cross-section: 120 mm²
- Permissible current rating buried 20°C: 386 A
- Permissible current rating buried/duct 20°C: 263 A
- Perm current rating in duct 30°C: 268 A
- Perm current rating in air 30°C: 346 A
4X16mm²
Nexans ref.
- Packaging: Drum (m)
- Conductor cross-section: 16 mm²
- Permissible current rating buried 20°C: 126 A
- Permissible current rating buried/duct 20°C: 89 A
- Perm current rating in duct 30°C: 80 A
- Perm current rating in air 30°C: 100 A
4X185mm²
Nexans ref.
- Conductor cross-section: 185 mm²
- Permissible current rating buried 20°C: 486 A
- Permissible current rating buried/duct 20°C: 332 A
- Perm current rating in duct 30°C: 340 A
- Perm current rating in air 30°C: 456 A
4X2.5mm²
Nexans ref. 10049387
- Packaging: Cut to length (m)
- Conductor cross-section: 2.5 mm²
- Permissible current rating buried 20°C: 38 A
- Permissible current rating buried/duct 20°C: 33 A
- Perm current rating in duct 30°C: 24 A
- Perm current rating in air 30°C: 32 A
4X240mm²
Nexans ref.
- Conductor cross-section: 240 mm²
- Permissible current rating buried 20°C: 563 A
- Permissible current rating buried/duct 20°C: 382 A
- Perm current rating in duct 30°C: 398 A
- Perm current rating in air 30°C: 538 A
4X25mm²
Nexans ref.
- Conductor cross-section: 25 mm²
- Permissible current rating buried 20°C: 161 A
- Permissible current rating buried/duct 20°C: 113 A
- Perm current rating in duct 30°C: 105 A
- Perm current rating in air 30°C: 127 A
4X35mm²
Nexans ref.
- Conductor cross-section: 35 mm²
- Permissible current rating buried 20°C: 194 A
- Permissible current rating buried/duct 20°C: 136 A
- Perm current rating in duct 30°C: 128 A
- Perm current rating in air 30°C: 158 A
4X4mm²
Nexans ref.
- Conductor cross-section: 4 mm²
- Permissible current rating buried 20°C: 59 A
- Permissible current rating buried/duct 20°C: 42 A
- Perm current rating in duct 30°C: 35 A
- Perm current rating in air 30°C: 42 A
4X50mm²
Nexans ref.
- Conductor cross-section: 50 mm²
- Permissible current rating buried 20°C: 230 A
- Permissible current rating buried/duct 20°C: 159 A
- Perm current rating in duct 30°C: 154 A
- Perm current rating in air 30°C: 192 A
4X6mm²
Nexans ref.
- Conductor cross-section: 6 mm²
- Permissible current rating buried 20°C: 74 A
- Permissible current rating buried/duct 20°C: 52 A
- Perm current rating in duct 30°C: 44 A
- Perm current rating in air 30°C: 54 A
4X70mm²
Nexans ref.
- Conductor cross-section: 70 mm²
- Permissible current rating buried 20°C: 282 A
- Permissible current rating buried/duct 20°C: 197 A
- Perm current rating in duct 30°C: 194 A
- Perm current rating in air 30°C: 246 A
4X95mm²
Nexans ref.
- Conductor cross-section: 95 mm²
- Permissible current rating buried 20°C: 339 A
- Permissible current rating buried/duct 20°C: 232 A
- Perm current rating in duct 30°C: 233 A
- Perm current rating in air 30°C: 298 A
5X1.5mm²
Nexans ref. 10040562
- Packaging: Cut to length (m)
- Conductor cross-section: 1.5 mm²
- Permissible current rating buried 20°C: 23 A
- Permissible current rating buried/duct 20°C: 19 A
- Perm current rating in duct 30°C: 19 A
- Perm current rating in air 30°C: 19 A
5X16mm²
Nexans ref.
- Packaging: Drum (m)
- Conductor cross-section: 16 mm²
- Permissible current rating buried 20°C: 126 A
- Permissible current rating buried/duct 20°C: 89 A
- Perm current rating in duct 30°C: 80 A
- Perm current rating in air 30°C: 100 A
5X185mm²
Nexans ref.
- Conductor cross-section: 185 mm²
- Permissible current rating buried 20°C: 486 A
- Permissible current rating buried/duct 20°C: 332 A
- Perm current rating in duct 30°C: 340 A
- Perm current rating in air 30°C: 456 A
5X2.5mm²
Nexans ref. 10040563
- Packaging: Cut to length (m)
- Conductor cross-section: 2.5 mm²
- Permissible current rating buried 20°C: 38 A
- Permissible current rating buried/duct 20°C: 33 A
- Perm current rating in duct 30°C: 24 A
- Perm current rating in air 30°C: 32 A
5X240mm²
Nexans ref.
- Conductor cross-section: 240 mm²
- Permissible current rating buried 20°C: 563 A
- Permissible current rating buried/duct 20°C: 382 A
- Perm current rating in duct 30°C: 398 A
- Perm current rating in air 30°C: 538 A
5X25mm²
Nexans ref.
- Packaging: Cut to length (m)
- Conductor cross-section: 25 mm²
- Permissible current rating buried 20°C: 161 A
- Permissible current rating buried/duct 20°C: 113 A
- Perm current rating in duct 30°C: 105 A
- Perm current rating in air 30°C: 127 A
5X35mm²
Nexans ref.
- Packaging: Cut to length (m)
- Conductor cross-section: 35 mm²
- Permissible current rating buried 20°C: 194 A
- Permissible current rating buried/duct 20°C: 136 A
- Perm current rating in duct 30°C: 128 A
- Perm current rating in air 30°C: 158 A
5X50mm²
Nexans ref.
- Conductor cross-section: 50 mm²
- Permissible current rating buried 20°C: 230 A
- Permissible current rating buried/duct 20°C: 159 A
- Perm current rating in duct 30°C: 154 A
- Perm current rating in air 30°C: 192 A
5X70mm²
Nexans ref.
- Packaging: Cut to length (m)
- Conductor cross-section: 70 mm²
- Permissible current rating buried 20°C: 282 A
- Permissible current rating buried/duct 20°C: 197 A
- Perm current rating in duct 30°C: 194 A
- Perm current rating in air 30°C: 246 A
5x10mm²
Nexans ref.
- Packaging: Cut to length (m)
- Conductor cross-section: 10 mm²
- Permissible current rating buried 20°C: 98 A
- Permissible current rating buried/duct 20°C: 68 A
- Perm current rating in duct 30°C: 60 A
- Perm current rating in air 30°C: 75 A
5x4mm²
Nexans ref.
- Packaging: Cut to length (m)
- Conductor cross-section: 4 mm²
- Permissible current rating buried 20°C: 59 A
- Permissible current rating buried/duct 20°C: 42 A
- Perm current rating in duct 30°C: 35 A
- Perm current rating in air 30°C: 42 A
5x6mm²
Nexans ref.
- Packaging: Cut to length (m)
- Conductor cross-section: 6 mm²
- Permissible current rating buried 20°C: 74 A
- Permissible current rating buried/duct 20°C: 52 A
- Perm current rating in duct 30°C: 44 A
- Perm current rating in air 30°C: 54 A
Description
Description
Standards
-
ProductIEC 60228; IEC 60502-1
-
TestIEC 60332-1-2; IEC 60332-3-24; IEC 60684-2; IEC 60754-1; IEC 60754-2; IEC 61034-2
Applications
Flexible power and control cable for fixed installations. To be used in locations where concentration of people is high: hospitals, malls, offices, classrooms, auditoriums, etc.
It can be installed in free air, in ducts or cable trays. In small sizes, it is used as control cable for the inner part in cabinets.
Construction: Singlecore or multicore copper conductor from 3 to 5 cores.
Conductor: Class 5 flexible copper conductor according to IEC 60228.
Insulation: Crosslinked Polyethylene (XLPE) with excellent electrical properties, good resistance to ozone and chemical agents. Cores identification by colors.
Oversheath: Black FREETOX® compound. Low fire hazard thermoplastic, halogen free, low smoke emission, flame and fire retardant, resistant to weather and UV radiation. Other colors upon request.
Marking: Nexans FREETOX-FLEX SERIE 3 RZ1-K "size" 0.6/1 kV 90°C "Certificate number" "Manuf. order" "Date" CHILE "sequential length"
Design Alternatives
FREETOX-FLEX-RAT: Resistant to rodent attack.
FREETOX-FLEX-BLIND: Shielded with copper tape.
FREETOX-FLEX-BLIND-TZ: Shielded with a tinned copper braid.
Other sizes or construction different to those included in the catalog.
INSTALATION CONDITIONS FOR CURRENT CARRYING CAPACITIES
Current carrying capacities based on table N°4.4 according to RIC N°4, They are applied for installations where ducts and cables are not directly exposed to solar radiation.
(3) direct current buried at 20°C: Sheathed, single conductor or multi conductor cables (Three conductors with load) installed directly buried. Installation Method D2 according to RIC N°4.
(4) current in buried duct at 20°C: Single conductor or multi conductor cables (three conductors with load) installed in buried ducts. Installation Method D1 according to RIC N°4.
(5) duct current at 30°C: Up to three single conductors or multi conductor cables (three conductors with load) installed in ducts or trays attached to walls. Installation Method B1 and B2 according to RIC N°4.
(6) air current at 30°C: Multiconductor cables (Three conductors with load) installed freely in the air, in conductor ladders or in conductor baskets or in perforated trays. Installation Method E according to RIC N°4. Single conductor cables: Three conductors with load, in contact and in a flat arrangement, installed freely in the air, on conductor ladders or in conductor baskets or in perforated trays. Installation Method F according to RIC N°4.
For buried installations, a depth of 0,7 meters and a thermal resistivity of the soil of 1 K*m/W.
Current capacity correction factors must be considered according to the specific installation conditions.
INSTALATION CONDITIONS FOR CURRENT CARRYING CAPACITIES
NOTES:
Values not defined as "maximum", "max.", "minimum" or "min." are not normative requirements in the standard and they are indicative only.
CERTIFICATE SEC RZ1-K (sections up to 35mm2 or 2AWG)
CERTIFICATE SEC RZ1-K (sections from 50mm2 to 1000mm2 or 1AWG to 1250kcmil)
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Mechanical characteristics
Mechanical characteristics